Some commercial humidifiers can spread Legionella under specific conditions. The design of the system decides whether those conditions can occur. That matters when you are reviewing an aerosol-producing system for a hospital or laboratory.
This article covers how Legionella establishes itself in humidification systems and the design variables that create or remove that risk. It also covers what ASHRAE Standard 188 asks of building water management programs. A closing checklist lists the documents infection control teams should request from any vendor.
This is general information for infection prevention, facilities and clinical engineering teams. It does not replace your own risk assessment. Check each source below in its current version.
Key Takeaways
- The Centers for Disease Control and Prevention (CDC) says Legionella grows best in water between 77°F and 113°F (25°C to 45°C). Stagnant water, biofilm and too little disinfectant also help it along. A system that lets water sit at indoor temperatures can meet several of those conditions at once.
- People most commonly get sick by breathing in mist that contains Legionella, according to the CDC. Any device that turns water into fine droplets needs a formal look at where that water has been.
- A 2024 case report in Microorganisms linked two sporadic legionellosis cases to domestic ultrasonic humidifiers. Legionella was found at high counts in the units. The report describes household devices rather than commercial equipment.
- Protozoa such as Acanthamoeba can colonize stagnant water and act as hosts in which Legionella multiplies. Biofilm gives the bacteria further protection from disinfectants.
- ASHRAE Standard 188 sets minimum legionellosis risk management requirements for building water systems. The Centers for Medicare & Medicaid Services (CMS) expects Medicare-certified hospitals to have water management policies in place.
- Five design questions matter in a humidifier. They cover standing water and water temperature at rest. Water treatment, recirculation and wetted surface area complete the list. No single answer settles risk.
- Ask every humidifier vendor for written water pathway documentation. Bring it to your water management program team before approval.
Need help sizing a humidification system?
Smart Fog’s engineers will size a system for your space, free.
Get a free sizing →How Legionella Establishes Itself in a Building Water System
Legionella occurs naturally in fresh water at low levels. It becomes a problem when it gets into a building’s plumbing or equipment and finds conditions that let it multiply.
The CDC’s public health strategy for Legionella control lists four conditions that let Legionella grow. A fifth, aerosol generation, decides whether it can then reach a person.
- Water temperature: Water sits in the range of 77°F to 113°F (25°C to 45°C).
- Stagnation: Slow-moving or stagnant water gives bacteria time to settle into surfaces.
- Biofilm: The CDC describes it as slime that provides a place for germs to grow.
- Disinfectant: There is not enough disinfectant in the water.
- Aerosol generation: The system produces droplets small enough to be inhaled.
Hot and cold water storage, long pipe runs with little flow and wet open surfaces all offer places for these conditions to line up. The enabling conditions can be present even when the supply looks clean on the day it enters the building. Mold is a separate mechanism, covered in our article on do commercial humidifiers cause mold.
Why Temperature and Stagnation Are the Core Risk Factors
Many indoor spaces sit comfortably inside the growth range, including heated mechanical rooms. Water that rests in a tank or line at room temperature between operating cycles can stay in that range for days. Stagnation adds to it, because the longer water sits, the more time bacteria have to settle into surfaces.
The CDC notes that Legionella may grow at temperatures as low as 68°F (20°C). Its guidance on monitoring building water recommends storing hot water above 140°F (60°C).
Biofilm and Protozoa as Amplification Mechanisms
Legionella persists and multiplies in biofilm layers on pipe walls, tank surfaces and reservoir interiors. The CDC says Legionella can live and grow in biofilm. Biofilm can also protect the bacteria from disinfectants.
Protozoa such as Acanthamoeba can add to the problem. They can act as intracellular hosts in which Legionella replicates, even at temperatures slightly outside the standard growth range. The 2024 case report discussed below isolated amoebae from samples at one of the homes it investigated.
Why Humidifiers Appear in Building Water Management Guidance
A humidifier takes building water and turns it into inhalable aerosol. The CDC states that people most commonly get sick by breathing in mist containing Legionella, as its page on how Legionella spreads explains. That is the same pathway that puts cooling towers, showerheads and decorative fountains under water management requirements.
The US Environmental Protection Agency (EPA) names humidifiers alongside showerheads and sink faucets as mist sources. Its page on Legionella in the indoor environment notes that breathing the mist or small droplets can cause infection. A facility-specific assessment, not the vendor’s classification of its own product, decides whether a given humidifier belongs in the program.
ASHRAE Standard 188 and Healthcare Facility Obligations
ASHRAE Standard 188-2021, Legionellosis: Risk Management for Building Water Systems, establishes minimum legionellosis risk management requirements for building water systems. Several sources shape what that means for a hospital.
- Scope of Standard 188: Its scope runs from design and construction through commissioning, operation and maintenance to repair, replacement and expansion. It applies to human-occupied commercial, institutional and industrial buildings, as well as multi-unit residential ones.
- ASHRAE Guideline 12: The guideline supplements the standard with more detail on specific water systems.
- CMS expectations: The CMS July 2022 interpretive guidance for hospital infection control sets expectations for Medicare-certified hospitals. Hospitals are expected to have water management policies and procedures that reduce the risk of Legionella growth and spread.
- What a documented program includes: CMS also says hospitals should consider a program that takes account of the ASHRAE standard and the CDC toolkit. A documented program includes a risk assessment, testing protocols with acceptable ranges for control measures and records of corrective action. The text is in CMS memorandum QSO-22-20.
- Humidifier scope: Ask your water management program coordinator whether a humidifier belongs in the scope of your program.
- ASHRAE Standard 170: Hospitals that humidify through air handlers should also read what ASHRAE Standard 170 says about humidifier water. Section 6.6 sets treatment, circulation and water purity requirements for adiabatic atomizing humidifiers. Your engineer of record can confirm how Standard 170 applies to your project.
- CDC toolkit: The CDC’s Legionella water management program toolkit explains how to develop a program.
The “It Creates a Mist” Concern Addressed at the Mechanism Level
Mist alone does not make a device hazardous. The hazard is mist made from water that has had a chance to grow Legionella. Your infection control team should therefore ask where that water comes from, how long it has sat and what it has touched.
Four factors set the risk: the water source, any standing volume, the water temperature and biofilm surfaces. A closed pathway that carries continuously flowing, treated water with no standing volume has a different risk profile from an open reservoir at ambient temperature. Dry surfaces in the treated room do not answer these questions, because the risk sits in the water pathway.
The Design Features That Raise or Lower Legionella Risk in Commercial Humidifiers
The five dimensions below work as a screening framework. For each one, the higher-risk pattern is described alongside a lower-risk pattern and a question to put to the vendor. They draw on the CDC’s growth conditions above and do not replace a facility assessment.
Standing water and reservoirs are the first dimension. They decide whether Legionella has a place to multiply.
- Higher-risk pattern: A tank or pan holds water between cycles, combining standing volume, indoor temperature and wetted surface. CDC guidance for humidifiers calls for tanks to be emptied and cleaned daily.
- Lower-risk pattern: There is no reservoir. The water path does not leave water sitting between cycles.
- Vendor question: Does the system hold standing water? What happens to the water in the supply lines when it is not running?
Water temperature at rest is the second dimension. It decides whether stored water can drift into the growth range.
- Higher-risk pattern: Water rests anywhere in the 77°F to 113°F range with no active control.
- Lower-risk pattern: Steam systems heat water far above the growth range to make steam. Upstream feedwater and any tanks still need attention. Single-pass systems manage risk by not letting water stand.
- Vendor question: What is the water temperature at each point on its way to the point where it enters the air?
Water supply and treatment is the third dimension. It sets the starting quality of the water.
- Higher-risk pattern: Untreated water feeds equipment with surfaces that stay wet and a long residence time.
- Lower-risk pattern: Treated water arrives with a documented specification and monitoring. Treatment changes the water in several ways. Ask how quality is kept in range after treatment.
- Vendor question: What water quality does the system need at its inlet? How is it monitored once it is running?
Recirculation and return lines are the fourth dimension. They decide whether stagnation compounds.
- Higher-risk pattern: Unused water returns to a tank and repeatedly crosses the same wetted surfaces.
- Lower-risk pattern: Water is used or discharged rather than looped back.
- Vendor question: Is any unused water returned or recirculated? How long does water stay in each part of the line?
Surface area for biofilm is the fifth dimension. It decides how many places biofilm can attach.
- Higher-risk pattern: Open tanks, wide distribution lines and collection surfaces offer attachment sites.
- Lower-risk pattern: Narrow, closed pathways with little wetted surface can be cleaned or drained.
- Vendor question: What surfaces does water touch between inlet and nozzle? Which cleaning protocol applies?
Why Reservoir-Based Systems Carry the Highest Risk
Open-reservoir humidifiers carry the highest risk. They include ultrasonic, evaporative and reservoir-fed spray systems. Ambient temperature, standing water and open surface area together create ideal growth conditions.
A 2024 case report of two sporadic legionellosis cases linked to domestic ultrasonic humidifiers shows the pattern. Both patients had limited mobility and were housebound. Legionella pneumophila serogroup 1 was found at high counts in their humidifiers.
The authors concluded that humidifiers can amplify pathogens when they are not cleaned and maintained properly. They recommended that humidifiers be considered in investigations of sporadic cases. The findings do not map directly onto commercial systems because these were household devices.
How Water Supply Type Affects Bacterial Load
Water treatment can change the starting quality of the water that reaches a humidifier. Reverse-osmosis (RO) and deionized (DI) water contains fewer dissolved minerals. That reduces the substrate available for biofilm and can lower the starting bacterial load.
The CDC lists scale, sediment and low disinfectant among the conditions that favor growth. Treated water that then sits at room temperature in a tank can still become a problem. Treat water quality as one input among several and ask for documents showing how the vendor manages all of them.
What Infection Control Teams Should Request From Any Humidification Vendor
Documentation that supports your ASHRAE Standard 188 program and the vendor’s design specifications together form the minimum evidence base for a facility risk assessment. The checklist that follows turns that evidence base into specific requests.
- Water pathway description: Request a written description of the water pathway, including whether a standing-water reservoir is present and whether water drains or purges between cycles.
- Water source and treatment documentation: Ask for the water quality the system needs at its inlet and any treatment the vendor specifies or supplies.
- Water management program compatibility: Check how the vendor has assessed the system against the program your facility maintains under Standard 188. Also request anything the vendor can supply to support your assessment.
- Recirculation documentation: Find out whether unused water is returned or discharged. Include how long water stays in each supply line.
- Maintenance records and schedule: Request the cleaning protocol for wetted internal surfaces, including interval and biofilm control steps.
- Water quality testing records or protocols: Look for any testing results from installed systems. If site-specific results do not exist, request the vendor’s testing protocol.
- Healthcare facility references: Ask for contacts at hospital or laboratory installations who agreed to speak with prospective customers.
The checklist applies to any vendor, not only Smart Fog. Verify vendor responses against your own infection control team’s requirements.
Why These Documents Matter for Joint Commission and CMS Compliance
CMS expects the hospital, not the vendor, to hold the water management program. The program is expected to show a risk assessment, control limits and corrective action records. Environment of Care standards from the Joint Commission also address water management programs.
A vendor who cannot supply a water pathway description leaves your team to reconstruct one from the equipment. That creates a compliance gap the facility must manage independently and slows approval. Smart Fog’s guide to humidifiers for hospitals and healthcare facilities covers how a hospital evaluates equipment more broadly.
Questions to Ask About Aerosol Generation Specifically
Infection control officers often focus on the mist itself. Four questions cover most of it:
- What is the water source at the point where droplets form? Has it passed through standing water first?
- Does water contact any open surface, such as a tank interior or collection tray, before it is atomized?
- What happens to water that does not evaporate? Does it pool, drain or return to a reservoir?
- What is the temperature of the water at the point where it enters the air?
Answers to these let your team assess risk at the mechanism level without needing to review the full system design alone.
How Smart Fog’s System Design Addresses Legionella Risk Factors
This section applies the risk framework above to Smart Fog systems for hospital and healthcare facility humidification. Smart Fog systems use patented self-evaporative adiabatic humidification, known as Dry Fog. Compressed air and water are mixed through a proprietary nozzle to produce an equal-sized droplet grid.
No humidification system removes the need for a water management program. This article does not claim that any Smart Fog system prevents or eliminates Legionella infection. Facilities should request Smart Fog’s water pathway documentation and system design specifications as part of a standard vendor evaluation, using the checklist above.
No Reservoir, RO/DI Input, and Closed Water Pathway
Three design characteristics map directly onto the risk variables above. Each one removes a specific condition from the Legionella growth list.
- No reservoir: The system has no open standing-water reservoir. That removes the primary Legionella amplification site.
- RO/DI input: The water supply is RO/DI-treated. It reduces dissolved mineral content and the substrate available for biofilm.
- Closed pathway: Water travels in a closed pathway from inlet to nozzle. With no recirculation, return lines cannot create stagnation.
Self-evaporating droplets absorb into the air before reaching surfaces under proper system design. That avoids the pooling and surface wetting that could support microbial growth in the treated space. Direct exposure to the fog stream will wet a surface.
Whether water sits in the lines between cycles depends on the model and installation. Request that detail in writing.
Documentation Smart Fog Can Provide for Healthcare Facility Evaluations
Infection control teams often ask for documentation on sales calls. System design specifications describing the water pathway and the RO/DI water quality requirements are available on request. Hospital references and infection control documentation depend on what exists for your project.
For hospital projects, start with our healthcare facility humidification systems page. Our laboratory humidification systems page covers laboratory settings. The Smart Fog technology overview describes the approach.
Our article on how humidity control supports infection prevention explains why holding humidity in range matters. The guide to hospital humidity control for patient safety covers the wider picture. For the risks of air that is too dry, read how low humidity increases infection risk in healthcare environments.
Final Thoughts
The real question for infection control is not whether a humidifier creates a mist. It is whether the system’s design lets Legionella multiply in water that then becomes the air your patients, staff or researchers breathe. The answer depends on the five design dimensions covered above.
Use the design framework and vendor checklist to compare any system on the same footing. Take the answers to your water management program team before anything is installed. To request system design documentation and a consultation for your hospital or laboratory, contact Smart Fog engineers.
FAQ
Can a commercial humidifier in a hospital cause Legionnaires’ disease?
A commercial humidifier can contribute to Legionnaires’ disease exposure if Legionella multiplies in the water it turns into inhalable mist. The risk depends on standing water, water temperature, treatment and cleaning rather than on the humidifier type alone. Each humidifier should be evaluated under the facility’s water management program.
What humidifier design features reduce Legionella risk in healthcare facilities?
Helpful features include no standing-water reservoir and no recirculation of unused water. A documented treatment specification and little wetted surface also help. Each facility’s own risk assessment decides what is acceptable, since no single feature removes risk.
Does ASHRAE Standard 188 require hospitals to include humidifiers in their water management plan?
ASHRAE Standard 188 sets minimum legionellosis risk management requirements for building water systems and their components, including those in hospitals. Whether a particular humidifier belongs in the program is decided by the facility’s own risk assessment, not the vendor. Program coordinators should review any humidifier that uses building water, since CMS expects Medicare-certified hospitals to have water management policies.
What is the temperature range in which Legionella grows in standing water?
Legionella grows best in water between 77°F and 113°F (25°C to 45°C), according to the CDC. Growth is possible at temperatures as low as 68°F (20°C). Many indoor spaces, including heated mechanical rooms, can hold water in that range.
Why are ultrasonic humidifiers considered higher risk for Legionella than other commercial types?
Ultrasonic humidifiers make mist directly from water held in a reservoir, usually without heating it. Reservoir water that stands at room temperature is therefore the concern. A 2024 case report in Microorganisms linked two sporadic legionellosis cases to household ultrasonic units with high Legionella counts.
What documentation should an infection control team request from a humidification vendor?
An infection control team should request seven categories of documents from any humidification vendor. The first four cover the water pathway, water source and treatment, program compatibility and recirculation. Maintenance records, testing records and healthcare references make up the rest.
Can a humidifier that produces a visible mist spread Legionella even if the room is not visibly wet?
In principle a humidifier can spread Legionella without leaving a room visibly wet, because fine droplets do not always leave moisture on surfaces. Legionella spreads when people breathe in mist that contains it. A dry room does not answer questions about reservoir water, biofilm in the pathway or supply treatment.
What water supply type reduces bacterial load in a commercial humidification system?
RO or DI treated water reduces dissolved minerals, scale and sediment that can feed biofilm. Treated water held at room temperature in a tank can still support growth. Treatment should be assessed together with temperature, stagnation and surface area.