Wet-Bulb Calculator
Enter the air temperature and relative humidity to find the wet-bulb temperature. See how much cooling evaporation could provide in a production space, air handler or gas turbine inlet.
Entering air conditions
101.325 kPa represents standard sea level. At elevation, use the local station pressure.
Cooling estimate
Calculating…
- Wet-bulb temperature
- —
- Maximum evaporative temperature drop
- —
- Estimated leaving-air temperature
- —
The maximum drop assumes complete saturation. The leaving-air estimate uses the effectiveness you entered. Actual performance depends on mixing, airflow and available evaporation distance.
What does the wet-bulb result mean?
The difference between dry-bulb and wet-bulb temperature is the evaporative cooling potential of the entering air. At 100% RH the two temperatures are equal, so the available drop is zero. Compare coincident temperature and RH readings from the same location and time.
For example, at 95°F, 40% RH and standard sea-level pressure, the wet-bulb temperature is about 75°F. At 80% effectiveness, the estimated leaving air is about 79°F. This is an airstream estimate. Heat from machinery and outdoor air exchange also affects the room temperature.
How the calculator works
The calculation uses the moist-air relationships in the ASHRAE Handbook—Fundamentals, Chapter 1. It solves the wet-bulb humidity-ratio equation at the entered atmospheric pressure. The leaving-air estimate subtracts the available temperature drop multiplied by the entered effectiveness from the entering dry-bulb temperature.
Use for dry-bulb temperatures from 32 to 131°F (0 to 55°C) and pressures from 60 to 110 kPa. For a facility estimate, check the maximum RH the process can tolerate downstream.