Humidity calculators

Wet-Bulb Calculator

Enter the air temperature and relative humidity to find the wet-bulb temperature. See how much cooling evaporation could provide in a production space, air handler or gas turbine inlet.

Entering air conditions

101.325 kPa represents standard sea level. At elevation, use the local station pressure.

Cooling estimate

Calculating…

The maximum drop assumes complete saturation. The leaving-air estimate uses the effectiveness you entered. Actual performance depends on mixing, airflow and available evaporation distance.

What does the wet-bulb result mean?

The difference between dry-bulb and wet-bulb temperature is the evaporative cooling potential of the entering air. At 100% RH the two temperatures are equal, so the available drop is zero. Compare coincident temperature and RH readings from the same location and time.

For example, at 95°F, 40% RH and standard sea-level pressure, the wet-bulb temperature is about 75°F. At 80% effectiveness, the estimated leaving air is about 79°F. This is an airstream estimate. Heat from machinery and outdoor air exchange also affects the room temperature.

How the calculator works

The calculation uses the moist-air relationships in the ASHRAE Handbook—Fundamentals, Chapter 1. It solves the wet-bulb humidity-ratio equation at the entered atmospheric pressure. The leaving-air estimate subtracts the available temperature drop multiplied by the entered effectiveness from the entering dry-bulb temperature.

Use for dry-bulb temperatures from 32 to 131°F (0 to 55°C) and pressures from 60 to 110 kPa. For a facility estimate, check the maximum RH the process can tolerate downstream.

Explore industrial evaporative cooling · Estimate turbine inlet cooling