...
Smart Fog solutions

Commercial & Industrial Humidification Systems

Dry-fog humidification systems for plants, warehouses, labs and commercial buildings. Smart Fog holds your humidity setpoint as weather, ventilation and production schedules change, without wetting floors or equipment.

  • Up to 25 lb/hr of humidity per unit on about 0.4 kW
  • Humidity held within about ±1–2% RH of setpoint
  • In-room, in-duct, portable and custom grid systems, with optional Modbus or BACnet
Illustrative control response

When a loading door opens

RH55%50%45%Door opensTime →
The shaded band marks an example target of 48–52% RH. As dry air enters, the controller calls for moisture and eases output as RH recovers.

Get commercial humidification system sizing and pricing

Tell us the space, the target humidity and what the humidity protects. A Smart Fog engineer replies with system sizing and a quote. Prefer to talk? Call 1-800-921-5230.

This field is for validation purposes and should be left unchanged.
Name(Required)
A sentence or two is enough. If you know your room size, duct airflow, or target humidity, you can include it here.

Commercial and industrial humidification system models

Every Smart Fog commercial humidification system uses the same dry-fog nozzle. The model sets how the fog reaches the air. Use this table to match a commercial humidifier system or an industrial humidification system to your space, then send us the room details for exact sizing.

ModelHow it is installedHumidity outputCompressed airWater supplyControls
ES100Wall-mounted, fogs directly into the space0–25 lb/hr (0–11 L/h), about 0.4 kW at maximum output4 CFM at 100 psi10 psiCPLC controller, optional Modbus or BACnet
TS100Inside new or existing ductwork0–25 lb/hr (0–11 L/h), about 0.4 kW at maximum output4 CFM at 100 psi10 psiCPLC controller, optional Modbus or BACnet
ES100MPortable unit on a wheeled baseUp to about 13 lb/hr (6 L/h)2 CFM at 100 psi10 psiRH sensor and controller
MS100Custom nozzle grid for large spacesSized to the project, up to 10,000 sq ft per systemSized to the projectSized to the projectZoned control, optional Modbus or BACnet

Larger commercial humidity control systems combine several units under one controller. Request sizing for your facility or estimate the moisture load yourself.

How industrial humidity control systems work

A commercial humidity control system measures relative humidity (RH), compares it with a setpoint, and adjusts moisture delivery as the load changes. For a printing plant, the process variable might be paper curl at press feed. For a museum, it might be a loan agreement’s allowable RH band. Define the material, location, permitted range and duration of excursions before selecting a humidifier.

Sense

Place a calibrated humidity sensor where the process experiences the air. A return-duct average can miss a dry loading area or a cold rack.

Control

Use the controller to call for humidification below the operating band and reduce output as conditions recover.

Verify

Trend readings at representative points during a door opening, ventilation change and low-load period. Check surfaces as well as the RH display.

Does the space need humidification or dehumidification?

Smart Fog adds moisture when a space is too dry. A space with excess moisture needs a different response. First compare local dew point with the temperature of the coldest exposed surfaces. Then check the HVAC system, makeup air and moisture released by the process.

ObservationEngineering check
RH falls on cold daysHeating cold outdoor air lowers its relative humidity. Check the moisture deficit and the amount of replacement air entering the building.
One line is dry while the return is on targetMap temperature, relative humidity and airflow near the product. Check sensor placement and zoning before increasing overall capacity.
Condensation appears on walls or equipmentMeasure surface temperature and local dew point. Check cold bridges, leakage and excess humidity before adding water.

Check the dew point at your process conditions.

Which failure shows up first in the product?

When humidity is low, paper and wood can lose moisture and change shape. Dry air can also increase static charge on insulating materials, which matters around sensitive electronics. At the other extreme, excess moisture can cause hygroscopic powders to clump and persistent condensation can promote corrosion. Use the observed failure to decide whether the zone needs humidification, dehumidification, or a change in temperature or airflow. Record representative conditions during both acceptable and rejected production.

Choose a control strategy for each zone

Rooms with different shifts, doors or exhaust schedules may need independent humidity control even when they share a building. An ES100 direct-space system can serve separate production areas. A TS100 in-duct system conditions a common supply airstream when airflow and evaporation distance allow. For temporary or changing work areas, review the ES100M mobile system.

Direct to the roomThe ES100 adds moisture within the production zone.
Through the supply ductThe TS100 adds moisture upstream of the spaces served by the air handler.

Smart Fog’s Self-Evaporating Droplets add water vapor as they evaporate. Available air moisture capacity, temperature and mixing govern that process. For in-duct installations, review airflow proving and downstream high-limit control with the HVAC designer. For in-room installations, leave room for the spray to evaporate before encountering equipment or materials.

How should two zones with different shifts be tested?

Log each zone during a shift change. If both rooms share supply air, compare their humidity trends when one line shuts down and its exhaust drops. If one room drifts while the other remains on target, review independent control before increasing total capacity. Compare room and duct humidity control →

What relative humidity should an industrial facility maintain?

Start with the product or process specification. A printer managing paper, a mushroom grower managing pinning, and an electronics assembler controlling static charge can need different conditions. Specify the normal setpoint, acceptable band, cold-surface limits, locations and hours of operation. A room-wide percentage alone cannot define success.

Printing and paper · Electronics and static control · Commercial mushroom growing

Size and commission the system

Quantify outdoor air, its design humidity ratio, internal moisture gains and the indoor target. Size maximum output for the design load, then check minimum controllable output on mild days. Fixed output that satisfies a busy shift can be too much when doors close or the exhaust turns down.

Agree on an acceptance test with operations: log actual RH and temperature in each zone, document response time, and review any period outside the agreed band. Check the sensor against a reference and record filtration and water-quality requirements for the maintenance team.

Estimate the required lb/h or kg/h →

Industrial humidity control by application

ProcessWhat changes with relative humidity?What to trend
Printing and convertingPaper exchanges moisture with air. Uneven moisture can contribute to curl and registration or feeding problems.RH at paper storage and press feed, shift changes and waste attributed to feeding.
Wood products and collectionsRepeated changes in moisture content can cause dimensional movement, warping or cracking.Product specifications, seasonal variations and RH at storage and assembly.
ElectronicsLow humidity can increase static electricity on some materials. Electrostatic discharge can damage sensitive devices.Protected-area RH, electrical verification records and exceptions to the ESD program.
Powders and sensitive productsExcess moisture can contribute to clumping or corrosion. Some processes need dehumidification during humid weather.Incoming air moisture, dew point, product evidence and process-specific limits.

How precise can the humidity control system be?

Smart Fog reports control within about ±1–2 percentage points of relative humidity in suitable installations. Specify where that band must be held and how it will be measured. Sensor accuracy, controller deadband and the spread between different workstations are three different measures. Verify the complete humidity control system at maximum and minimum load before accepting the result.

Can heating or air conditioning control humidity alone?

Heating changes relative humidity by changing temperature. It does not add water vapor. A cooling coil can remove water if its surface is below dew point. An industrial humidity control system coordinates moisture addition with these HVAC effects, including dehumidification where the process requires both directions of control. Insulation and drainage also matter when high humidity or condensation affects walls and machinery.

How should you set the humidity band for a new zone?

In ordinary occupied buildings, the EPA’s moisture-control guidance for schools and commercial buildings recommends keeping relative humidity below 60%, ideally between 30% and 50% where possible. Production areas can have different requirements. Set the process target with the people responsible for the product and check what the building envelope can tolerate in winter. EPA · Moisture control in commercial buildings.

For example, a print line may specify 45–55% RH to stabilize paper, while a produce room or mushroom fruiting chamber may require higher humidity to reduce moisture loss. Pharmaceutical operations may need dehumidification to protect moisture-sensitive materials. Keeping adjacent areas at different humidity levels requires attention to doors, makeup air and where the sensors are located.

What do low and high humidity look like in practice?

Very dry air can increase static electricity and cause hygroscopic products to lose moisture, change dimension or warp. Excess humidity can promote powder clumping, condensation, mold growth on persistently damp materials and corrosion on susceptible surfaces. Repair leaks or cold-surface problems that repeatedly wet the same area. The controller can change air moisture, but cannot repair a leak.

How do you compare humidification methods?

A steam system adds generated steam to the airstream. An adiabatic humidifier evaporates water into the air and provides a cooling effect. A refrigeration coil or desiccant system removes excess moisture. Estimate the required capacity in each direction before comparing choices. Record both heating and cooling loads, water quality and maintenance obligations for the year.

Smart Fog system features

Smart Fog designs its systems around Self-Evaporating Droplets, fog fine enough to evaporate in the air before it reaches a surface, with a reported characteristic diameter of about 4.2 μm. The nozzle has no moving parts. System sizing, water treatment, air distribution and sensor placement determine how the installed system performs. Include available compressed air, electrical service and water quality in the proposal request.

Explore the droplet and control graphicsES100 direct spaceTS100 in ductES100M mobileMS100 custom grid

Commercial humidification system FAQs

What is a commercial humidification system?

A commercial humidification system adds moisture to a whole room, zone or building and holds it at a setpoint. It combines humidity sensors, a controller and one or more fog units, unlike a portable room humidifier that runs on its own with no feedback.

How do I size an industrial humidification system?

Sizing starts from the moisture load: room volume, air changes, outdoor conditions and the target relative humidity. One ES100 or TS100 delivers up to 25 lb/hr, and several units combine for larger loads. Use the humidifier sizing calculator for a first estimate or send us the room details for a sized proposal.

How much energy does a dry-fog system use?

An ES100 or TS100 draws about 0.4 kW at maximum output, based on average compressed air use. The fog evaporates in the air, so no boiler or heating element is needed to make steam.

What utilities does the system need?

Each ES100 or TS100 needs compressed air at 4 CFM and 100 psi, a water supply at about 10 psi and electrical service for the controls.

Can it connect to a building management system?

Yes. An optional integration package supports Modbus or BACnet so the system can report to and take setpoints from your BMS.